Our products are manufactured by deft professionals using high-end raw materials as per the exact demand and need of the clients. In order to meet different requirements of the customers, we are offering the array of our products in various specifications and dimensions and the customers are facilitated to avail the range as per their need and requirement through our unmatched customization facility.
Parameters | Performance | |||||||||
Make | “AVIONICSS” | |||||||||
Capacity | 100 KVA | |||||||||
Transformer Type | Main Transformer | |||||||||
Stabilizer Type | 3 Phase, 4 Wire, Linear Unbalanced Type | |||||||||
Safety Functions (Optional) As per demand by the Purchaser | High / Low Cut & Overload Function | |||||||||
Phase Prevention | ||||||||||
Servo Bypass | ||||||||||
Type of cooling | ONAN (Oil Cooled | |||||||||
Application | Indoor Type | |||||||||
Duty cycle at frequency | 100% continuous at 50Hz AC supply | |||||||||
Temp. Rise | 35˚C | |||||||||
Winding Temp. Rise | 40˚C | |||||||||
Input voltage range | 340v-470v (P-P) / 196V- 270V (P-N), 50 Hz, AC | |||||||||
Output Voltage range | 410V, +/- 1% (P-P) / 235V, +/- 1% (P-N) | |||||||||
Manually Adjustable | ||||||||||
Core Used | CRGO M4 grade or better(0.23-0.27 mm) | |||||||||
Copper Used | Electrolytic grade (99.97$\% pure) | |||||||||
Insulation | Class A | |||||||||
Regulation | 1% From no load to full load | |||||||||
Regulator Coils | Linear Coils | |||||||||
Rate of Correction | 10 – 15V/sec (Up to 1000KVA) | |||||||||
Operating Frequency | 47Hz – 50Hz | |||||||||
Efficiency | Better than 98% | |||||||||
Effect of load P.F | Nil | |||||||||
Metering | Digital metering for phase & current | |||||||||
Wave Form Distortion | Nil | |||||||||
Response Time | Less than 100ms. | |||||||||
Over load Capacity | 120% for 30 mins Momentarily | |||||||||
Conductor | High Grade Copper Strip | |||||||||
Mounting | Unidirectional wheels | |||||||||
Design & Testing Standards | IS 9815 / IS 2026 | |||||||||
No Load Losses | Less than 0.8% over entire range | |||||||||
Oil used | High strength transformer oil | |||||||||
First filling of oil | Included | |||||||||
Expected Working Life | More Than 25 Years |